Description
1. The meter can be called a universal analog input display meter. It can be matched with various sensors with analog output to display the actual physical quantity. Such as temperature transmitter, frequency converter, motor speed, preure, liquid level, concentration, etc.
2. The instrument supports current input or voltage input.
3. Default adaptation: 0-10V, 2-10V, 0-20mA, 4-20mA. By setting the bias parameter and gain parameter, it can adapt to other inputs in the range of 0-10V, or 0-20mA.
4. It is displayed as a percentage by default. You can also set your own display range through F0-2 ~ F0-4.
5. The instrument with 485 interface has already supported the communication between the meters, and it is convenient to realize multiple displays.
Main features
Model description,standard version: HXDSBOXAI-NR;With RS485 version: HXDSBOXAI-485;With relay output version: HXDSBOXAI-RL
Standard version and version with RS485, rated power supply voltage range: DC6~25V, power consumption: 24V/40mA;with relay output version, rated power supply voltage Range: DC8~25V, powerconsumption: 24V/50mA;power supply anti-reverse connection and surge protection
1 analog input, voltage type or current type can be selected
Voltage type input impedance: >30kQ, current type input impedance:
"With RS485 version", using standard Modbus-RTU protocol, easy to achieve networking: and support networking between tables,"With relay output version", with 1 normally open relay output, relay load capacity: 3A30Dc/3A250VAC;
Mechanical size: 794325mm: installation opening: 76.539.5mm.
Indicator light and signal description
1.Front panel diagram
2. Indicator light:
a. Only "with RS485 version" is useful: R communication receives data indication: T communication sends data indication
b. Only the "with relay output version" has: S indicator light on when the relay is closed
3.Port signal description
signal
Explanation
PWR
Connectto the positive pole of the power supply (standard version and versionwith RS485: DC6~30V: with relay output version: DC8~30V)
GND
Power and signal ground
Ai
Power and signal ground
mA
Current-type analog input signal configuration interface, short-circuited with A, then configured as current-type input
WithRS485 version
485-
RS485 signal is negative
485+
RS485 signal is positive
With relay outputversion
KA
Relay normally open contact output port
KB
4.Common wiring diagram:
5. Button and digital tube display state transition diagram:
Special note: In the third-level menu, click OK to save the modified parameter value and return to the previous menu, the parameter number is automatically increased by one; and click the SET button to directly return to the previous menu without saving the modified parameter value .Long pre
or
to make the adjustment value change quickly.
Parameter description
The parameters are described as follows:
1.F0 Attendant array display
Parameter
parameter name
Scope and description
Defaults
Read write
F0-0
Collected value monitoring
Monitor the percentage of the current analog input value. Range: 0-100.0%
read-only
F0-1
Display value monitoring
In the display value in "Monitoring Menu" is calculated by F0-0, F0-2~F04.
read-only
F0-2
Display accuracy
The number of decimal places displayed in the "Monitor Menu", range: 0-3.
1
Read write
F0-3
Show minimum
In the "monitoring menu", the value corresponding to "acquisition value" is 0%, the range: -1999~9999
0
Read write
F0-4
Show maximum
In the "Monitoring Menu", the value corresponding to the "Acquisition Value" is 100.0%, the range: 1999~9999
1000
Read write
F0-5
Offline status
0: Not disconnected; 1: Disconnected. (Disconnection detection is set by F1-4) (starting from V2.10)
read-only
2.F1 parameter group-analog configuration parameters
Parameter
parameter name
Scope and description
Defaults
Read write
F1-0
Input type selection
0: 0~10V or 0~20mA corresponds to 0~100.0%;
1: 2~10V or 4~20mA corresponds to 0~100.0%, and 0 when it is lower than 2V or 4mA.
0
Read write
F1-1
Input filter time
Analog input filter time, range: 0~10.000s. The longer the filtering time, the stronger the filtering
0.200
Read write
F1-2
Input gain
Range: 0~1000.0%.
100.0
Read write
F1-3
Input offset
-99.9~99.9%, with 10V or 20mA as 100.0%.
0.0
Read write
F1-4
Drop detection threshold
Range: 0.0-100.0%. This value is based on 0-10V or 0-20mA as 0.0-100.0% as a reference (and
F1-0 and gain offset are not related), the detection is not started if it is le than 0.5, and there is a hysteresis of 0.3.
When the input signal is lower than this value, the meter displays E.oFL. (Starting from V2.10)
0.0
Read write
F1-5
Enter the parameter setting select
-
Fruugo ID:
279403132-621274316
-
EAN:
9085801629309
Product Safety Information
Please see the product safety information specific to this product outlined below
The following information is provided by the independent third-party retailer selling this product.
Product Safety Labels
Safety Warnings:
-
Keep out of reach of children: Prevent accidental ingestion, misuse, or harm.
-
Always follow instructions: Ensures proper usage and prevents malfunctions or accidents.
Delivery & Returns
Dispatched within 24 hours
Shipping from China.
We do our best to ensure that the products that you order are delivered to you in full and according to your specifications. However, should you receive an incomplete order, or items different from the ones you ordered, or there is some other reason why you are not satisfied with the order, you may return the order, or any products included in the order, and receive a full refund for the items. View full return policy