Kuvaus
Feature:
1. Strong anti-interference ability, can be connected to external high-current AC contactor and relay, will not crash under strong electromagnetic interference.
2. The product is resistant to high temperatures and can work in the environment of -40 to 85 ° C.
3. Industrial grade products. Support automatic acquisition of IP.
4. The true 100M speed enables reliable communication with 0 delay commands.
5. Support 10 TCP client connections under the TCP server.
6. Through the provided configuration software, you can configure five working modes: TCP server, TCP client, UDP server, UDP client, DNS domain name.
7. 8-way relay, 8-channel digital input with full-open and full-off input. With power-down save function (save relay status).
8. With an RS485 port, it supports Ethernet to RS485 transparent transmission.
Specification:
Item Type:Network Relay
Power Supply:DC7~24V(DC socket or wiring terminal can be selected to input power.)
DC Connector Size:5.5 x 2.1mm / 0.22 x 0.08in(Outer Diameter - Inner Diameter)
Working Temperature Range:-40~85℃
Users Manual:
8 independent relay outputs
10 channels of independent input
IN9 means full open, after IN9 has digital input, all relays are connected.
IN10 means full off. When IN10 has output, all relays are off.
The 8-input user of IN1-IN8 can be configured into three different working modes through the configuration parameter tool, and is selected under the “Input Mode” of the configuration tool.
In the "normal input" mode, the ordinary input signal is acquired. To obtain the input status, a command to read the input status is sent to the device.
"Trigger Relay" mode, after this mode has input, the corresponding relay state is reversed, and the IN1-IN8 control corresponds to the 1-8 relay.
Active Upload mode, which actively sends an input status to the network connected to the device when there is a change in the input.
The device has an RS485 interface. It can be controlled by RS485 equipment from other manufacturers. Can realize the transparent transmission of network data to RS485 data, the baud rate 300-115200 can be configured. When using parity, the data bit must be configured to 9 bits, and the serial port parameters are configured through the configuration tool.
The device has a power-down save function that saves the status of the relay and can be configured through the configuration tool.
Reset the configuration. The label RESET position is the factory reset button.
Working mode introduction
The working mode is configured with the provided configuration software.
1, TCP server
In this mode, the device can only be connected through the TCP client and supports the connection of 10 TCP clients.
2, TCP client
In this mode, the device actively connects to the TCP server (remote IP and remote port number are parameters for device connection). Only one server can be connected.
3, UDP server
In this mode, any UDP communication is supported.
4, UDP client
In this mode, only UDP communication is supported for remote IP and remote port number (configuration software settings).
5, DNS domain name
In this mode, the device connects to the TCP server (the port is the remote port) that binds the domain name with a TCP client.
Command interpretation
The above commands are sent and received in characters. There is no carriage return after the command, no spaces. To be hexadecimal, you need to check the ASCII code table to convert itself.
Get device name
Send: name
Return: name="HHC-N8I8OP"
The HHC-N8I8OP is the device name and can be configured using the configuration tool.
Control the first relay
Send: on1
Return: on1
Turn off the first relay
Send: off1
Return: off1
The command format is on and off followed by the relay channel, and the 2-8 control is the same as above.
Control all relays
Send: all00000011
Return: relay00000011
All is to control all relay commands, the latter 8 channels control, 1 means pull-in, 0 means to loosen the above command to indicate that the first road is connected with the second road, and the third road is released. After this instruction is executed, it returns to the state of the relay. The status information of the relay is the same as the information returned by the read command.
Delay control
For example, if you want the relay to pick up and then release it for 2 seconds, you can send the following command.
Send: on1:02
Return: on1
The above command indicates that the relay is released after 2 seconds of pull-in, on1: indicates the relay to be controlled, followed by the delay time, maximum 99 seconds, for example, on2:12 means that the second relay is released after 12 seconds of pu
-
Fruugo ID:
334845402-737583899
-
EAN:
7695727649279
Tuoteturvallisuustiedot
Katso tätä tuotetta koskevat tuoteturvallisuustiedot alla
Seuraavat tiedot tarjoaa tätä tuotetta myyvä riippumaton kolmas osapuoli.
Tuoteturvallisuustarrat
Turvallisuusvaroitukset:
Warning: Please read the product instructions carefully before use to ensure correct use.
Sarjanumero:
7695727649279